IndMALL 2.0 preview — for review only, not indexed by search engines. Links reflect the live IndMALL site; WhatsApp buttons open the real IndMALL enquiry number.

Industrial automation products & suppliers across India

EL1259 - Beckhoff EtherCAT Terminal

Image for reference. Refer to the datasheet for exact dimensions.

EL1259 - Beckhoff EtherCAT Terminal

Mail Us for Beckhoff EtherCAT Terminal EL1259 with exclusive offers. 1-wire, 24 V DC (-15), 0…55°C, 8…9 mm.

Brand
Beckhoff
Model number
EL1259

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Beckhoff EL1259 technical specifications

Connection technology1-wire
Nominal voltage24 V DC (-15%/+20%)
“0” signal voltage-3...+5 V (IEC 61131-2, type 1/3)
“1” signal voltage11..30 V (IEC 61131-2, type 1/3)
Input currenttyp. 3 mA (EN 61131-2, type 1/3)
Input filtertyp. < 1 µs
Distributed clocksyes
Current consumption power contactstyp. 30 mA + load
Current consumption E-bustyp. 130 mA
Electrical isolation500 V (E-bus/field potential)
Configurationno address or configuration setting
Special featuresmulti-timestamping, auto activation
Weightapprox. 55 g
Operating temperature0…55°C
Storage temperature-25…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable (see documentation)
Approvals/markingsCE, UL
Housing - Design formHD (High Density) housing with signal LEDs
Housing - Materialpolycarbonate
Housing - Dimensions (W x H x D)12Â mm x 100Â mm x 68 mm
Housing - Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Housing - Side by side mounting by means ofdouble slot and key connection
Housing - Markinglabeling of the BZxxxx series
Housing - Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Housing - Connection cross-sections*: 0.08…1.5 mm²,st*: 0.25…1.5 mm²,f*: 0.14…0.75 mm²
Housing - Connection cross-section AWGs*: AWG28...16,st*: AWG22...16,f*: AWG26...19
Housing - Stripping length8…9 mm
Housing - Current load power contactsImax: 10 A
Distributed clock precision<< 1 µs
Internal sampling/execution< 10…40 µs, corresponds to 100…25 k detectable edges/s, dependent on configuration
Number of channels8 inputs + 8 outputs
Load typeohmic, inductive, lamp load
Max. output current0.5 A (short-circuit proof) per channel
Output stagepush
Reverse voltage protectionyes
Breaking energy< 150 mJ/channel
Switching timestyp. TON: < 1 µs, typ. TOFF: < 1 µs
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

EL1259 Beckhoff EtherCAT Terminal Technical Specifications