Image for reference. Refer to the datasheet for exact dimensions.
EP1809-0042 - Beckhoff EtherCAT Box Digital Input
The Beckhoff EP1809-0042 is an EtherCAT Box: number of inputs 16, bus interface 2 x M12 socket, 4-pin, D-coded.
- Brand
- Beckhoff
- Model number
- EP1809-0042
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Beckhoff EP1809-0042 key specifications
| Type | EtherCAT Box |
|---|---|
| Protocol | EtherCAT |
| Bus interface | 2 x M12 socket, 4-pin, D-coded |
| Specification | EN 61131-2, type 1/3 |
| Number of inputs | 16 |
| Input connections | M12 x 1, 5-pin, A-coded |
| Nominal input voltage | 24 V DC (-15%/+20%) |
| Input filter | typ. 3 ms |
| Signal voltage “0” | -3…+5 V (EN 61131-2, type 3) |
| Signal voltage “1” | 11…30 V (EN 61131-2, type 3) |
| Input current | typ. 3 mA (EN 61131-2, type 3) |
| Power supply connection | feed: 1 x 7/8" plug, 5-pin; downstream connection: 1 x 7/8" socket, 5-pin |
| Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total |
| Current consumption from US | typ. 130 mA |
| Electrical isolation | 500 V |
| Weight | approx. 440 g |
| Operating temperature | -25…+60°C |
| Degree of protection | IP65 |
Beckhoff EP1809-0042: frequently asked questions
How many channels does the EP1809-0042 have?
Number of inputs: 16.
Which bus connection does the EP1809-0042 use?
Bus interface: 2 x M12 socket, 4-pin, D-coded; Protocol: EtherCAT.
Is the EP1809-0042 electrically isolated?
Electrical isolation: 500 V.
What temperature range is the EP1809-0042 rated for?
Operating temperature: -25…+60°C.