Image for reference. Refer to the datasheet for exact dimensions.
EP1819-0021 - Beckhoff EtherCAT Box Digital Input
The Beckhoff EP1819-0021 is an EtherCAT Box: number of inputs 16, bus interface 2 x M8 socket, 4-pin, A-coded, shielded.
- Brand
- Beckhoff
- Model number
- EP1819-0021
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Beckhoff EP1819-0021 key specifications
| Type | EtherCAT Box |
|---|---|
| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, 4-pin, A-coded, shielded |
| Specification | EN 61131-2, type 1/3 |
| Number of inputs | 16 |
| Input connections | M8 x 1, 3-pin, A-coded |
| Nominal input voltage | 24 V DC (-15%/+20%) |
| Input filter | typ. 10 µs |
| Signal voltage “0” | -3…+5 V (EN 61131-2, type 3) |
| Signal voltage “1” | 11…30 V (EN 61131-2, type 3) |
| Input current | typ. 3 mA (EN 61131-2, type 3) |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, A-coded |
| Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total |
| Current consumption from US | typ. 130 mA |
| Electrical isolation | 500 V |
| Weight | approx. 250 g |
| Operating temperature | -25…+60°C |
| Degree of protection | IP65 |
Beckhoff EP1819-0021: frequently asked questions
How many channels does the EP1819-0021 have?
Number of inputs: 16.
Which bus connection does the EP1819-0021 use?
Bus interface: 2 x M8 socket, 4-pin, A-coded, shielded; Protocol: EtherCAT.
What temperature range is the EP1819-0021 rated for?
Operating temperature: -25…+60°C.
What is the IP rating of the EP1819-0021?
IP65.