Beckhoff EP2816-0008 key specifications
| Type | EtherCAT Box |
|---|---|
| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, 4-pin, A-coded, shielded |
| Number of outputs | 16 |
| Output connections | D-sub socket, 25-pin, UNC4-40 |
| Load type | resistive, inductive, lamp load |
| Nominal output voltage | 24 V DC (-15%/+20%) |
| Max. output current | 0.5 A per channel, individually short-circuit proof, ∑ 4 A |
| Switching times | typ. TON: 60 µs, typ. TOFF: 300 µs |
| Short-circuit current | max. 1.5 A |
| Distributed clocks | yes |
| Current consumption from US | 120 mA |
| Auxiliary power current | typ. 20 mA + load |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, A-coded |
| Electrical isolation | 500 V |
| Weight | approx. 165 g |
| Operating temperature | -25…+60°C |
| Degree of protection | IP65 |
Beckhoff EP2816-0008: frequently asked questions
How many channels does the EP2816-0008 have?
Number of outputs: 16; Load type: resistive, inductive, lamp load.
Which bus connection does the EP2816-0008 use?
Bus interface: 2 x M8 socket, 4-pin, A-coded, shielded; Protocol: EtherCAT.
Does the EP2816-0008 support distributed clocks?
Yes. Distributed clocks: yes.
Is the EP2816-0008 electrically isolated?