Image for reference. Refer to the datasheet for exact dimensions.
Pepperl Fuchs KCD2-SLD-Ex1-1045 Solenoid Driver
Mail Us for P&F Line Fault Transparency Solenoid Drivers KCD2-SLD-Ex1-1045 with exclusive offers. 1-channel isolated barrier, Output 45 mA at 10 V DC.
- Brand
- Pepperl Fuchs
- Model number
- KCD2-SLD-Ex1-1045
- Series
- Pepperl Fuchs Solenoid Drivers
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Pepperl Fuchs KCD2-SLD-Ex1-1045 technical specifications
| Signal type | Digital Output |
|---|---|
| Safety Integrity Level (SIL) | SIL 3 |
| Systematic capability (SC) | SC 3 |
| Supply Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered |
| Rated voltage | 19 ... 30 V DC loop powered |
| Rated current | - |
| Power dissipation | 75 mA at 24 V, 220 Ω load |
| Power consumption | 1.4 W at 24 V, 220 Ω load |
| Connection side (Input) | control side |
| Connection (Input) | terminals 5+, 6- |
| Signal Level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC |
| Inrush current(Input) | < 200 mA , 10 ms loop powered |
| Connection side (Output) | field side |
| Connection (Output) | terminals 1+, 2- |
| Internal resistor | 285 Ω |
| Current | typ. 45 mA |
| Voltage | typ. 10 V |
| Output current | 45 mA |
| Switching frequency | - |
| Display elements | LED |
| Control elements | DIP switch |
| Labeling | space for labeling at the front |
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) |
| Connection | screw terminals |
| Mounting | on 35 mm DIN mounting rail |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 |
| Mass | approx. 150 g |
Overview
The Pepperl Fuchs KCD2-SLD-Ex1-1045 Solenoid Driver offers a Digital Output signal type, on 35 mm DIN mounting rail , and screw terminals connection. Obtain a Quote for P&F Line Fault Transparency Solenoid Driver KCD2-SLD-Ex1-1045. The control side provides 1-signal voltage of 19-30 V DC (loop powered) or 15-30 V DC (bus powered) and 0-signal voltage of 0-5 V DC, supporting currents up to 200 mA with a 10 ms response time. The device dimensions are 12.5 x 119 x 114 mm, and it mounts on a 35 mm DIN rail. Operating temperatures range from -20 to 60 °C, with an IP20 rating, and it weighs approximately 150 g.
Datasheet
Pepperl Fuchs datasheetpepperl-fuchs-kcd2-sld-ex1-1045.pdfOther models in this series
Compare KCD2-SLD-Ex1-1045 with similar models in the same series. See all 20 models on the Pepperl Fuchs Solenoid Drivers page.
| Model | Connection | Output current | Rated voltage | Voltage |
|---|---|---|---|---|
| KCD2-SLD-Ex1-1045 (this model) | screw terminals | 45 mA | 19 ... 30 V DC loop powered | typ. 10 V |
| KCD0-SD3-Ex1-1045 | screw terminals | 45 mA | loop powered | ≥ 10 V |
| KCD0-SD3-Ex1-1245 | screw terminals | 45 mA | loop powered | ≥ 12 V |
| KCD0-SD3-Ex1-1245-SP | screw terminals | 45 mA | loop powered | ≥ 12 V |
| KCD2-SLD-Ex1-1065 | screw terminals | 65 mA | 19 ... 30 V DC loop powered | typ. 10 V |
| KCD2-SLD-Ex1-1245 | screw terminals | 50 mA | 19 ... 30 V DC loop powered | typ. 12 V |
| KFD0-SD2-Ex1-10100 | screw terminals | 100 mA | 20 ... 35 V DC , loop powered | ≥ 9.5 V |
| KFD0-SD2-Ex1-1180 | screw terminals | 80 mA | 21 ... 35 V DC , loop powered | ≥ 11 V |