Image for reference. Refer to the datasheet for exact dimensions.
Pepperl Fuchs KFD2-STC5-Ex1-2O-H Transmitter Power Supplies
Ask for the Pricing of P&F 2-wire and 3-wire Smart Transmitter Power Supplies KFD2-STC5-Ex1-2O-H with exclusive offers. 1-channel, 4 mA -20 mA current.
- Brand
- Pepperl Fuchs
- Model number
- KFD2-STC5-Ex1-2O-H
- Series
- Pepperl Fuchs Transmitter Power Supplies
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Pepperl Fuchs KFD2-STC5-Ex1-2O-H technical specifications
| Signal type | Analog input |
|---|---|
| Safety Integrity Level (SIL) | SIL 2 |
| Systematic capability (SC) | SC 3 |
| Supply Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 18 ... 30 V DC |
| Ripple | within the supply tolerance |
| Rated current | - |
| Power dissipation | ≤ 1 W at maximum load |
| Power consumption | ≤ 1.7 W at maximum load |
| Connection side (Input) | field side |
| Connection (Input) | terminals 1+, 2-, 3 |
| Input signal | 4 ... 20 mA |
| Open circuit voltage/short-circuit current (Input) | terminals 1+, 3: 24 V / 25 mA |
| Input resistance | max. 265 Ω terminals 2-, 3 , max. 330 Ω terminals 1+, 3 |
| Available voltage | ≥ 17 V at 20 mA ; ≥ 21 V at 4 mA , terminals 1+, 3 |
| Connection side (Output) | control side |
| Connection (Output) | terminals 7+, 8-, 9-; 10+, 11-, 12- (sink), terminals 7-, 8+, 9+; 10-, 11+, 12 (source) |
| Load | 0 ... 600 Ω |
| Output signal | 4 ... 20 mA (overload > 25 mA) |
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB), control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
| Settling time | 200 µs |
| Display elements | LED |
| Labeling | space for labeling at the front |
| Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) |
| Connection | screw terminals |
| Mounting | on 35 mm DIN mounting rail |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 |
| Mass | approx. 200 g |
Overview
The Pepperl Fuchs KFD2-STC5-Ex1-2O-H Transmitter Power Supplies offers a Analog input signal type, on 35 mm DIN mounting rail , and screw terminals connection. Ask for the Pricing of P&F 2-wire and 3-wire Smart Transmitter Power Supplies KFD2-STC5-Ex1-2O-H at unbeatable prices. Detailed Specifications of 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) features Analog input with Analog input with 4 ... 30 V DC it consumes ≤ 1 W at maximum load. The unit measures 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , mounts on a 45mm DIN rail, and operates between -20 ... 60 °C (-4 ...
Datasheet
Pepperl Fuchs datasheetkfd2-stc5-ex1-2o-h.pdfOther models in this series
Compare KFD2-STC5-Ex1-2O-H with similar models in the same series. See all 19 models on the Pepperl Fuchs Transmitter Power Supplies page.
| Model | Connection | Connection (Input) | Supply Connection | Open circuit voltage/short-circuit current (Input) |
|---|---|---|---|---|
| KFD2-STC5-Ex1-2O-H (this model) | screw terminals | terminals 1+, 2-, 3 | Power Rail or terminals 14+, 15- | terminals 1+, 3: 24 V / 25 mA |
| KFD2-STC5-Ex1-H | screw terminals | terminals 1+, 2-, 3 | Power Rail or terminals 14+, 15- | terminals 1+, 3: 24 V / 25 mA |
| KCD2-STC-Ex1-2O-DE | screw terminals | terminals 1+, 2- (sink); 3+, 4- (source) | Power Rail or terminals 9+, 10- | terminals 3, 4: ≤ 6.1 V at 20 mA |
| KCD2-STC-Ex1-ES-SP | spring terminals | terminals 1+, 2-; 3+, 4- | Power Rail or terminals 9+, 10- | - |
| KCD2-STC-Ex1-SP | spring terminals | terminals 1+, 2-; 3+, 4- | Power Rail or terminals 9+, 10- | terminals 1+, 2-: 22 V / 26 mA |
| KFD2-STC4-Ex1 | screw terminals | terminals 1+, 2-, 3 or 5-, 6+ | Power Rail or terminals 14+, 15- | - |
| KFD2-STC4-Ex1-2O | screw terminals | terminals 1+, 2-, 3 or 5-, 6+ | Power Rail or terminals 14+, 15- | terminals 1+, 3-: 22.7 V / 38 mA |
| KFD2-STC4-Ex1-H | screw terminals | terminals 1+, 2-, 3 or 5-, 6+ | Power Rail or terminals 14+, 15- | - |
| KFD2-STC4-Ex2 | screw terminals | terminals 1+, 3-; 4+, 6- | Power Rail or terminals 14+, 15- | - |