Pepperl Fuchs KFU8-CRG2-Ex1.D technical specifications
| Signal type | Analog input |
|---|---|
| Safety Integrity Level (SIL) | SIL 2 |
| Supply Connection | terminals 23, 24 |
| Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC |
| Ripple | - |
| Rated current | - |
| Power dissipation | 2 W / 3 VA |
| Power consumption | 2.2 W / 4 VA |
| Programming Interface | programming socket |
| Connection side (Input) | field side |
| Connection (Input) | terminals 1, 2, 3 |
| Input signal | 0/4 ... 20 mA |
| Available voltage | > 15 V at 20 mA |
| Open circuit voltage/short-circuit current (Input) | 24 V / 33 mA |
| Input resistance | 45 Ω (terminals 2, 3) |
| Line fault detection | breakage I < 0.2 mA; short-circuit I > 22 mA |
| Connection side (Output) | control side |
| Connection (Output) | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- |
| Output signal | 0 ... 20 mA or 4 ... 20 mA |
| Output I, II | signal, relay |
| Output III | Signal, analog |
| Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output III/power supply and collective error | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Interface/power supply and collective error | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs , display |
| Control elements | Control panel |
| Configuration | via operating buttons via PACTware |
| Labeling | space for labeling at the front |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/35/EU | EN 61010-1:2010 |
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | 300 g |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | TÜV 01 ATEX 1701 |
| Marking | Ex-Hexagon II (1)G [Ex ia Ga] IIC Ex-Hexagon II (1)D [Ex ia Da] IIIC Ex-Hexagon I (M1) [Ex ia Ma] I |
| Input | Ex ia |
| Maximum safe supply voltage | 253 V AC (Attention! The rated voltage can be lower.) |
| IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| IECEx certificate | IECEx TUN 09.0007 |
| UL approval | - |
| FM approval(Control drawing) | 16-554FM-12 (cFMus) |
Overview
The Pepperl Fuchs KFU8-CRG2-Ex1.D Trip Amplifier offers a Analog input signal type, signal, relay output, and screw terminals connection. Ask for the Pricing of P&F Line Fault Detection Trip Amplifier KFU8-CRG2-Ex1.D at unbeatable prices. Detailed Specifications of Ex ia features Analog input with 0/4 ... 20 mA range, SIL 2 and terminals 23, 24 ratings. 140 °F), has an IP50 rating, and mounts on a 55 mm DIN rail. Measuring 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 , and weighing 300 g, it includes LEDs, a display, and control panel for easy operation.
Datasheet
Pepperl Fuchs datasheetkfu8-crg2-ex1.d.pdfOther models in this series
Compare KFU8-CRG2-Ex1.D with similar models in the same series. See all 4 models on the Pepperl Fuchs Trip Amplifier page.
| Model | Input | Input signal | Open circuit voltage/short-circuit current (Input) | Output I, II |
|---|---|---|---|---|
| KFU8-CRG2-Ex1.D (this model) | Ex ia | 0/4 ... 20 mA | 24 V / 33 mA | signal, relay |
| KFD2-GUT-Ex1.D | Ex ia | - | - | relay |
| KFD2-WAC2-Ex1.D | - | 0/4 ... 20 mA | 18 V / 5 mA | Relay output |
| KFU8-GUT-Ex1.D | Ex ia | - | - | relay |