Image for reference. Refer to the datasheet for exact dimensions.
Schneider ATV610C11N4 Variable Speed Drive
Schneider ATV610C11N4, Easy Altivar 610 Variable Speed Drive. Ensure reliable performance—request your IndMALL quote today for efficient solutions.
- Brand
- Schneider
- Model number
- ATV610C11N4
- Series
- Altivar 610
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Schneider ATV610C11N4 technical specifications
| Mounting mode | Cabinet mount |
|---|---|
| Height | 850 mm1161 mm with IP21 conformity kit |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bitsAI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bitsAI2, AI3 software-configurable temperature probe or water level sensor |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
| Range of product | Easy Altivar 610 |
| Ambient air temperature for operation | -15…45 °C (without derating)45…60 °C (with derating factor) |
| Communication port protocol | Modbus serial |
| Operating position | Vertical +/- 10 degree |
| Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog inputAQ1, AQ2: +/- 0.2 % for analog output |
| Product destination | Asynchronous motorsSynchronous motors |
| IP degree of protection | IP20 |
| number of preset speeds | 16 preset speeds |
| Line current | 201 A at 380 V (normal duty)175.7 A at 460 V (normal duty)170 A at 380 V (heavy duty)149.1 A at 460 V (heavy duty) |
| Braking to standstill | By DC injection |
| Number of Units in Package 2 | - |
| Analogue input number | 3 |
| Output voltage | <= power supply voltage |
| Analogue output type | Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bitsSoftware-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
| Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Sampling duration | 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input5 ms +/- 1 ms (DI5, DI6)configurable - pulse input10 ms +/- 1 ms (AQ1, AQ2) - analog output |
| Depth | 375 mm |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 sS, U or customized |
| Product specific application | Fan, pump, compressor, conveyor |
| Continuous output current | 211 A at 2.5 kHz for normal duty173 A at 2.5 kHz for heavy duty |
| Apparent power | 140.0 kVA at 460 V (normal duty)118.8 kVA at 460 V (heavy duty) |
| Product or component type | Variable speed drive |
| Width | 300 mm |
| Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
| Maximum transient current | 232 A during 60 s (normal duty)260 A during 60 s (heavy duty) |
| Physical interface | 2-wire RS 485 for Modbus serial |
| EMC filter | Integrated conforming to IEC 61800-3 category C3 with 50 m |
| Discrete input type | DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhmDI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
| Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output |
| Ambient air temperature for storage | - |
| Noise level | 76 dB conforming to 86/188/EEC |
| Relay output number | 3 |
| Discrete input logic | Positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1)Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1) |
| Connector type | 1 RJ45 (on the remote graphic terminal) for Modbus serial |
| Relay Output Type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
| Net Weight | 85.5 kg |
| Motor power hp | 150 hp for normal duty125 hp for heavy duty |
| Electrical connection | Control, screw terminal: 0.5...1.5 mm²Line side, screw terminal: 2 x 50...3 x 120 mm²Motor, screw terminal: 3 x 50...3 x 120 mm² |
| Transmission frame | RTU for Modbus serial |
| Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V ACRelay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DCRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V ACRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Analogue output number | 2 |
| Switching frequency | 1...8 kHz adjustable |
| Motor power kW | 110 kW for normal duty90 kW for heavy duty |
| Supply frequency | 50...60 Hz +/-5 % |
| Output frequency | 0.1…500 Hz |
| Protection type | Thermal protection: motorMotor phase break: motorThermal protection: driveOverheating: driveOvercurrent between output phases and earth: driveOverload of output voltage: driveShort-circuit protection: driveMotor phase break: driveOvervoltages on the DC bus: driveLine supply overvoltage: driveLine supply undervoltage: driveLine supply phase loss: driveOverspeed: driveBreak on the control circuit: drive |
| Type of cooling | Forced convection |
Overview
The Schneider ATV610C11N4 is a high-efficiency 110 kW Variable Speed Drive (VSD) engineered for three-phase industrial motor applications. Three analog inputs and two analog outputs allow flexible configuration for voltage (0–10 V) or current (0–20 mA) signals, enabling precise motor speed control and process feedback. For communication, the Schneider ATV610C11N4 integrates an RS-485 Modbus serial interface that seamlessly connects with PLC and SCADA systems. The enclosure offers IP20 protection with an optional IP21 kit and an integrated EMC filter compliant with IEC 61800-3 Category C3 standards. The Schneider ATV610C11N4 is widely used in HVAC systems, pumps, fans, compressors, and conveyor drives where precise speed regulation and energy optimization are critical.
Datasheet
Schneider datasheetschneider-electric-atv610c11n4.pdfOther models in this series
Compare ATV610C11N4 with similar models in the same series. See all 20 models on the Altivar 610 page.
| Model | Depth | Height | Switching frequency | Width |
|---|---|---|---|---|
| ATV610C11N4 (this model) | 375 mm | 850 mm1161 mm with IP21 conformity kit | 1...8 kHz adjustable | 300 mm |
| ATV610D90N4 | 323 mm | 762 mm922 mm with EMC plate | 1...8 kHz adjustable | 290 mm |
| ATV610D55N4 | 323 mm | 762 mm922 mm with EMC plate | 1...8 kHz adjustable | 290 mm |
| ATV610C13N4 | 375 mm | 850 mm1161 mm with IP21 conformity kit | 1...8 kHz adjustable | 300 mm |
| ATV610D45N4 | 271 mm | 613 mm706 mm with EMC plate | 2...12 kHz adjustable | 226 mm |
| ATV610D30N4 | 271 mm | 613 mm706 mm with EMC plate | 2...12 kHz adjustable | 226 mm |
| ATV610D22N4 | 232 mm | 495 mm580 mm with EMC plate | 2...12 kHz adjustable | 211 mm |
| ATV610D37N4 | 271 mm | 613 mm706 mm with EMC plate | 2...12 kHz adjustable | 226 mm |
| ATV610D75N4 | 323 mm | 762 mm922 mm with EMC plate | 1...8 kHz adjustable | 290 mm |