IndMALL 2.0 preview — for review only, not indexed by search engines. Links reflect the live IndMALL site; WhatsApp buttons open the real IndMALL enquiry number.

Industrial automation products & suppliers across India

LR9D5569: Schneider Electric Tesys LRD Thermal Protection Adjustment

Image for reference. Refer to the datasheet for exact dimensions.

LR9D5569: Schneider Electric Tesys LRD Thermal Protection Adjustment

Schneider LR9D5569, Tesys LRD Thermal Protection Adjustment. Ensure motor safety—request a quote from IndMALL today and optimize motor performance.

Brand
Schneider
Model number
LR9D5569
Series
Schneider Contactors TeSys Deca Overload Relay

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Schneider LR9D5569 technical specifications

Device short nameLR9D
RangeTeSys
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height118 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping in 4 s +/- 20 % conforming to IEC 60947-4-1
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
Thermal overload classClass 20 conforming to IEC 60947-4-1
Network typeAC
Tripping threshold1.05 +/- 0.06 In alarm conforming to IEC 60947-4-11.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessVibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsULCSACCCUKCA
Depth125 mm
Width115 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range90…150 A
Tightening torqueAlarm circuit: 0.45 N.m - on screw clamp terminalsPower circuit: 18 N.m - on bars M8Control circuit: 1.2 N.m - on screw clamp terminals
Mounting supportUnder contactorRail
Relay applicationMotor protection
Net weight0.885 kg
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

Technical Specifications of Schneider Electric Tesys LRD Thermal Protection Adjustment LR9D5569: Ask for the Pricing of Schneider Electric Tesys LRD Thermal Protection Adjustment LR9D5569 at unbeatable prices. Detailed Specifications of LR9D5569 features device short name LR9D, from the TeSys range. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 118 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The control type consists of a Red push-button: stopBlue push-button: reset.

Datasheet

Schneider datasheetschneider-electric-lr9d5569.pdf

Other models in this series

Compare LR9D5569 with similar models in the same series. See all 107 models on the Schneider Contactors TeSys Deca Overload Relay page.

LR9D5569 compared with other models in the series
ModelRangeThermal protection adjustment range[Uimp] rated impulse withstand voltageNetwork type
LR9D5569 (this model)TeSys90…150 A6 kV conforming to IEC 60947-1AC
LRD1514TeSys7…10 A6 kVACDC
LR2D3553TeSys23…32 A6 kVACDC
LRD1510TeSys4…6 A6 kVACDC
LRD3361TeSys55…70 A6 kV conforming to IEC 60947-1DCAC
LRD4369TeSys110…140 A6 kV conforming to IEC 60947-1DCAC
LRD3322TeSys17…25 A6 kV conforming to IEC 60947-1DCAC
LRD106TeSysTeSys Deca4…6 A6 kVACDC
LRD10LTeSysTeSys Deca4…6 A6 kVACDC