IndMALL 2.0 preview — for review only, not indexed by search engines. Links reflect the live IndMALL site; WhatsApp buttons open the real IndMALL enquiry number.

Industrial automation products & suppliers across India

LRD325: Schneider Electric Industrial Application Thermal Relay

Image for reference. Refer to the datasheet for exact dimensions.

LRD325: Schneider Electric Industrial Application Thermal Relay

Schneider LRD325, Industrial Application Thermal Relay. Protect motors—get a quote from IndMALL today and improve your motor protection solutions.

Brand
Schneider
Model number
LRD325
Series
Schneider Contactors TeSys Deca Overload Relay

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Schneider LRD325 technical specifications

Device short nameLRD
RangeTeSysTeSys Deca
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height70 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Thermal overload classClass 10A conforming to IEC 60947-4-1
Network typeDCAC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessShocks: 15 Gn for 11 ms conforming to IEC 60068-2-7Vibrations: 4 gn conforming to IEC 60068-2-6
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSACCCEACDNV-GLRMRSEU-RO MRLROS (Lloyds register of shipping)ATEX INERISUKCA
Permissible current0.95 A at 380 V AC-15 for signalling circuit0.06 A at 440 V DC-13 for signalling circuit
Depth123 mm
Width55 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range17…25 A
Flame retardanceV1 conforming to UL 94
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 5 N.m - on EverLink BTR screw connectors
Mounting supportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor
Relay applicationMotor protection
Net weight0.375 kg
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

Technical Specifications of Schneider Electric Industrial Application Thermal Relay LRD325: Talk to Our Engineer for Schneider Electric Industrial Application Thermal Relay LRD325 with exclusive offers. Core System Specifications of LRD325 are device short name LRD, from the TeSysTeSys Deca range. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 70 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The control type consists of a Red push-button: stopBlue push-button: reset.

Datasheet

Schneider datasheetschneider-electric-lrd325.pdf

Other models in this series

Compare LRD325 with similar models in the same series. See all 107 models on the Schneider Contactors TeSys Deca Overload Relay page.

LRD325 compared with other models in the series
ModelRangeThermal protection adjustment range[Uimp] rated impulse withstand voltageNetwork type
LRD325 (this model)TeSysTeSys Deca17…25 A6 kVDCAC
LRD223TeSysTeSys Deca16…24 A6 kVACDC
LRD02TeSysTeSys Deca0.16…0.25 A6 kVDCAC
LRD1512TeSys5.5…8 A6 kVDCAC
LRD103TeSysTeSys Deca4…6 A6 kVDCAC
LRD350LTeSysTeSys Deca37…50 A6 kVACDC
LRD01TeSysTeSys Deca0.1…0.16 A6 kVDCAC
LRD4367TeSys95…120 A6 kV conforming to IEC 60947-1ACDC
LRD1514TeSys7…10 A6 kVACDC