Schneider LRD3314 technical specifications

Device short nameLRD
RangeTeSys
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height81 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Thermal overload classClass 10A conforming to IEC 60947-4-1
Network typeDC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
[Ue] rated operational voltage1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSACCCEACUKCACE
Permissible current3 A at 120 V AC-15 for signalling circuit0.22 A at 125 V DC-13 for signalling circuit
Depth115 mm
Width70 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength2.2 kV at 50 Hz conforming to IEC 60947-1
Relay applicationMotor protection
Net weight0.51 kg
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

Technical Specifications of Temperature Compensation In Schneider Relay LRD3314: Obtain a Quote for Temperature Compensation In Schneider Relay LRD3314 at economical prices. Specifications Overview for LRD3314 reveals device short name LRD, from the TeSys range. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 81 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The auxiliary contact composition includes 1 NO + 1 NC, and it features a thermal overload Class 10A conforming to IEC 60947-4-1. The control type consists of a Red push-button: stopBlue push-button: reset.

Datasheet

Schneider datasheetschneider-electric-lrd3314.pdf

Other models in this series

Compare LRD3314 with similar models in the same series. See all 107 models on the Schneider Contactors TeSys Deca Overload Relay page.

LRD3314 compared with other models in the series
ModelRangeThermal protection adjustment range[Uimp] rated impulse withstand voltageNetwork type
LRD3314 (this model)TeSys—6 kVDC
LRD226TeSysTeSys Deca16…24 A6 kVDCAC
LRD326TeSysTeSys Deca23…32 A6 kVDCAC
LRD32LTeSysTeSys Deca23…32 A6 kVDCAC
LRD33696TeSys110…140 A6 kVACDC
LRD340LTeSysTeSys Deca30…40 A6 kVACDC
LRD3656TeSysTeSys Deca48…65 A6 kVDCAC
LRD3321TeSys12…18 A6 kVDC
LRD3312TeSys5.5…8 A6 kVDC