Beckhoff EP4314-1002 key specifications
| Type | EtherCAT Box |
|---|---|
| Protocol | EtherCAT |
| Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
| Number of outputs | 2 (single-ended) |
| Number of inputs | 2 x analog (single-ended), 2 x digital |
| Input/output connections | M12 x 1, 5-pin, a-coded |
| Signal type | ±10 mA, ±20 mA, 0…20 mA, 4…20 mA, parameterizable per channel |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Load | output: < 500 Ω |
| Internal resistance | input: 85 Ω typ. + diode voltage |
| Resolution | 16 bit |
| Conversion time | input: ~ 100 µs, output: ~ 40 µs |
| Measurement error/uncertainty | input: < 0.3%, output: < 0.1% (each relative to full scale value) |
| Actuator supply | from the auxiliary voltage UP |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Electrical isolation | 500 V |
| Current consumption from US | 120 mA |
| Operating temperature | -25…+60°C |
Beckhoff EP4314-1002: frequently asked questions
How many channels does the EP4314-1002 have?
Number of inputs: 2 x analog (single-ended), 2 x digital; Number of outputs: 2 (single-ended); Nominal voltage: 24 V DC (-15%/+20%).
Which bus connection does the EP4314-1002 use?
Bus interface: 2 x M8 socket, 4-pin, a-coded, shielded; Protocol: EtherCAT.
What temperature range is the EP4314-1002 rated for?
Operating temperature: -25…+60°C.
What resolution does the EP4314-1002 have?
Resolution: 16 bit; Conversion time: input: ~ 100 µs, output: ~ 40 µs; Measurement error/uncertainty: input: < 0.3%, output: < 0.1% (each relative to full scale value).