Image for reference. Refer to the datasheet for exact dimensions.
Delta RTU-EN01 Programmable Logic Controller Module
Delta RTU-EN01 Programmable Logic Controller (PLC) from the DVP-S Series offers Ethernet remote I/O, RS-485, 24 VDC power, and multi-protocol communication.
- Brand
- Delta
- Model number
- RTU-EN01
- Series
- DVP-S Series
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Delta RTU-EN01 technical specifications
| Power Supply Voltage | 24 VDC (-15 to 20%) |
|---|---|
| Power consumption | 2 W |
| Storage /Operation Temperature | Storage: -25ºC ~70ºC (temperature)Operation: 0ºC ~55ºC (temperature) |
| Storage /Operation humidity | 5%~95% (humidity)5%~95% (humidity); pollution degree 2 |
| Vibration/shock immunity | International standards: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) |
| Transmission method | RS-485 |
| Connector | Removable |
| Serial baudrate | 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps |
| Data type | Modbus ASCII/RTU |
| Noise immunity | ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air DischargeEFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,Communication I/O: ±2KVRS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/mConducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150kHz ~ 80MHz, 3V/mSurge Test (Biwave IEC61132-2, IEC61000-4-5): Power line 0.5KV DM, Ethernet 0.5KVCM, RS-485 0.5KV CM |
| Transmission interface | RJ-45 MDI/MDIX, no jumper cable required |
| Baudrate | 10/100M bps, auto-detection |
| Network protocols | ICMP, IP, TCP, UDP, DHCP, NTP, Modbus TCP, HTTP |
| Insulation voltage | 500 V |
Overview
Delta RTU-EN01 Programmable Logic Controller module is designed for automation systems where remote I/O expansion and reliable network communication are required. This Delta PLC module functions as an Ethernet-based remote I/O unit, enabling seamless data exchange between controllers and field devices. The module operates on a 24VDC supply with efficient power usage, making it suitable for continuous operation in control panels. Its Ethernet interface allows efficient data transmission between control units and remote devices, while the RS-485 interface supports additional field connectivity. It enables system integrators to connect multiple devices, manage data exchange, and extend system functionality without complex wiring. The compact design supports easy installation within control panels.
Datasheet
Delta datasheetdvp-series.pdfOther models in this series
Compare RTU-EN01 with similar models in the same series. See all 205 models on the DVP-S Series page.
| Model | Number of Outputs and Type | Fuse Capacity | Power consumption | Program capacity |
|---|---|---|---|---|
| RTU-EN01 (this model) | — | — | 2 W | — |
| DVP20SX211T | Analog (2), Relay (6) | 2A/ 250VAC; SV: 2.5A/ 30VDC | 4W | 16k Steps |
| DVP20PM00D | — | 2A/ 250VAC | 60 VA | 64K Steps |
| DVP20PM00M | — | 2A/ 250VAC | 60 VA | 64K Steps |
| DVP10PM00M | 16 | 2A/ 250VAC | 60VA | 64k steps |
| DVP20PM00DT | 8 | 2A/ 250VAC | 60 VA | 64k steps |
| DVP10MC11T | 4 Outputs | 3 A/30 VDC, Polyswitch | 8 W Max | Ladder 16k steps / Motion 1Mbyte |
| RTU-485 | Transmission method: RS-485 · Connector: 3-pin, removable · Data type: Modbus ASCII/RTU | |||
| RTU-DNET | Transmission method: CAN · Connector: Removable, 5.08mm · Message type: Explicit, I/O polled | |||