Image for reference. Refer to the datasheet for exact dimensions.
LC1K090087M7: Schneider 4P 230V AC Contactors
Schneider LC1K090087M7, 4P 230V AC Contactors. Boost system efficiency—ask IndMALL for pricing today and optimize your system’s control.
- Brand
- Schneider
- Model number
- LC1K090087M7
- Series
- Schneider Contactors TeSys K Contactors
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Schneider LC1K090087M7 technical specifications
| Connections - terminals | Faston terminals 2 cable(s) (external diameter: 2.8 mm) Faston terminals 1 cable(s) (external diameter: 6.35 mm) |
|---|---|
| [Uc] control circuit voltage | 220...230 V AC 50/60 Hz |
| Minimum switching voltage | - |
| contactor application | Resistive load |
| Width | 45 mm |
| Control circuit type | AC at 50/60 Hz |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| Depth | 57 mm |
| [Ie] rated operational current | 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit |
| Auxiliary contacts type | - |
| poles description | 4P |
| Auxiliary contact composition | - |
| IP degree of protection | IP2X conforming to VDE 0106 |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508Power circuit: 690 V conforming to IEC 60947-4-1Power circuit: 600 V conforming to CSA C22.2 No 14 |
| Operating altitude | 2000 m without derating |
| Ambient air temperature for operation | - |
| Power pole contact composition | 2 NO + 2 NC |
| Hold-in power consumption in W | - |
| Ambient air temperature for storage | -50…80 °C |
| Utilisation category | AC-1 |
| Insulation resistance | - |
| Heat dissipation | 1.3 W |
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
| Net weight | 0.18 kg |
| Minimum switching current | - |
| Mounting support | RailPlate |
| Operating time | 10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing15...25 ms coil de-energisation and NC closing5...15 ms coil energisation and NC opening |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947 |
| Product or component type | Contactor |
| Tightening torque | - |
| Maximum operating rate | 3600 cyc/h |
| Range | TeSys |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC <= 400 HzSignalling circuit: <= 690 V AC <= 400 Hz |
| Height | 58 mm |
| Motor power kW | - |
| Inrush power in W | - |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Electrical durability | 0.16 Mcycles 20 A AC-1 at Ue <= 690 V |
| Device short name | LC1K |
Overview
Technical Specifications of Schneider 4P 230V AC Contactors LC1K090087M7: Obtain a Quote for Schneider 4P 230V AC Contactors LC1K090087M7 at economical prices. Specifications Overview for LC1K090087M7 reveals control circuit voltage [Uc] operates at 220...230 V AC 50/60 Hz, with a minimum switching voltage of -, ensuring responsive operation. The control circuit type is AC at 50/60 Hz, and the auxiliary contacts are - configuration, providing reliable switching. The sensor features a 4P design and operates at altitudes up to 2000 m without derating, ensuring versatility across various environments. Heat dissipation 1.3 W, it is energy efficient. Our commitment to better pricing and exceptional support sets us apart from other Competitors.
Datasheet
Schneider datasheetschneider-electric-lc1k090087m7.pdfOther models in this series
Compare LC1K090087M7 with similar models in the same series. See all 120 models on the Schneider Contactors TeSys K Contactors page.
| Model | [Uc] control circuit voltage | Minimum switching voltage | Hold-in power consumption in VA | Hold-in power consumption in W |
|---|---|---|---|---|
| LC1K090087M7 (this model) | 220...230 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09004P7 | 230 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09004U7 | 230...240 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K090083E7 | 48 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K090085E7 | 48 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K090087S7 | 500 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09008P7 | 230 V AC 50/60 Hz | - | 4.5 VA (at 20 °C) | - |
| LC1K09015M7 | 220...230 V AC 50/60 Hz | 17 V for signalling circuit | 4.5 VA (at 20 °C) | - |
| LC1K0901G7 | 120 V AC 50/60 Hz | 17 V for signalling circuit | 4.5 VA (at 20 °C) | - |