IndMALL 2.0 preview — for review only, not indexed by search engines. Links reflect the live IndMALL site; WhatsApp buttons open the real IndMALL enquiry number.

Industrial automation products & suppliers across India

LC1K09015M7: Schneider 3P Contactor For Automation Systems

Image for reference. Refer to the datasheet for exact dimensions.

LC1K09015M7: Schneider 3P Contactor For Automation Systems

Schneider LC1K09015M7, 3P Contactor for Automation Systems. Maximize performance—request a quote from IndMALL today and boost your operations.

Brand
Schneider
Model number
LC1K09015M7
Series
Schneider Contactors TeSys K Contactors

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Schneider LC1K09015M7 technical specifications

Connections - terminalsSolder pins (external diameter: 0.035 mm)
[Uc] control circuit voltage220...230 V AC 50/60 Hz
Minimum switching voltage17 V for signalling circuit
contactor applicationResistive loadMotor control
Width45 mm
Control circuit typeAC at 50/60 Hz
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
Depth57 mm
[Ie] rated operational current9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Auxiliary contacts typetype instantaneous 1 NC
poles description3P
Auxiliary contact composition1 NC
IP degree of protectionIP2X conforming to VDE 0106
[Ui] rated insulation voltagePower circuit: 600 V conforming to UL 508Power circuit: 690 V conforming to IEC 60947-4-1Signalling circuit: 690 V conforming to IEC 60947-4-1Signalling circuit: 690 V conforming to IEC 60947-5-1Signalling circuit: 600 V conforming to UL 508Power circuit: 600 V conforming to CSA C22.2 No 14Signalling circuit: 600 V conforming to CSA C22.2 No 14
Operating altitude2000 m without derating
Ambient air temperature for operation-
Power pole contact composition3 NO
Hold-in power consumption in W-
Ambient air temperature for storage-50…80 °C
Utilisation categoryAC-3AC-3eAC-1AC-4
Insulation resistance> 10 MOhm for signalling circuit
Heat dissipation1.3 W
Hold-in power consumption in VA4.5 VA (at 20 °C)
Net weight0.18 kg
Minimum switching current5 mA for signalling circuit
Mounting supportPrinted circuit boards
Operating time10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing
Rated breaking capacity110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947
Product or component typeContactor
Tightening torque-
Maximum operating rate3600 cyc/h
RangeTeSys
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 HzSignalling circuit: <= 690 V AC <= 400 Hz
Height58 mm
Motor power kW2.2 kW at 220...230 V AC 50/60 Hz AC-34 kW at 380...415 V AC 50/60 Hz AC-34 kW at 440/690 V AC 50/60 Hz AC-32.2 kW at 220...230 V AC 50/60 Hz AC-3e4 kW at 380...415 V AC 50/60 Hz AC-3e4 kW at 440/690 V AC 50/60 Hz AC-3e2.2 kW at 220...230 V AC 50/60 Hz AC-44 kW at 380...415 V AC 50/60 Hz AC-44 kW at 440/690 V AC 50/60 Hz AC-4
Inrush power in W-
[Uimp] rated impulse withstand voltage8 kV
Electrical durability1.3 Mcycles 9 A AC-3 at Ue <= 440 V1.3 Mcycles 9 A AC-3e at Ue <= 440 V0.16 Mcycles 20 A AC-1 at Ue <= 690 V0.02 Mcycles 54 A AC-4 at Ue <= 440 V
Device short nameLC1K
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

Technical Specifications of Schneider 3P Contactor For Automation Systems LC1K09015M7: Please speak to our Technical Engineer for Schneider 3P Contactor For Automation Systems LC1K09015M7 at attractive prices. Technical Specs Summary of LC1K09015M7 includes control circuit voltage [Uc] operates at 220...230 V AC 50/60 Hz, with a minimum switching voltage of 17 V for signalling circuit, ensuring responsive operation. The control circuit type is AC at 50/60 Hz, and the auxiliary contacts are type instantaneous 1 NC configuration, providing reliable switching. The sensor features a 3P design and operates at altitudes up to 2000 m without derating, ensuring versatility across various environments. Heat dissipation 1.3 W, it is energy efficient.

Datasheet

Schneider datasheetschneider-electric-lc1k09015m7.pdf

Other models in this series

Compare LC1K09015M7 with similar models in the same series. See all 120 models on the Schneider Contactors TeSys K Contactors page.

LC1K09015M7 compared with other models in the series
Model[Uc] control circuit voltageMinimum switching voltageHold-in power consumption in VAHold-in power consumption in W
LC1K09015M7 (this model)220...230 V AC 50/60 Hz17 V for signalling circuit4.5 VA (at 20 °C)-
LC1K090085E748 V AC 50/60 Hz-4.5 VA (at 20 °C)-
LC1K090087M7220...230 V AC 50/60 Hz-4.5 VA (at 20 °C)-
LC1K090087S7500 V AC 50/60 Hz-4.5 VA (at 20 °C)-
LC1K09008P7230 V AC 50/60 Hz-4.5 VA (at 20 °C)-
LC1K0901G7120 V AC 50/60 Hz17 V for signalling circuit4.5 VA (at 20 °C)-
LC1K0901P7230 V AC 50/60 Hz17 V for signalling circuit4.5 VA (at 20 °C)-
LC1K0910U7230...240 V AC 50/60 Hz17 V for signalling circuit4.5 VA (at 20 °C)-
LC1K1201E748 V AC 50/60 Hz17 V for signalling circuit4.5 VA (at 20 °C)-