IndMALL 2.0 preview — for review only, not indexed by search engines. Links reflect the live IndMALL site; WhatsApp buttons open the real IndMALL enquiry number.

Industrial automation products & suppliers across India

Sick RLY3-EMSS300 Safety Relay

Image for reference. Refer to the datasheet for exact dimensions.

Sick RLY3-EMSS300 Safety Relay

Obtain a Quote for Sick N/O Output Safety Relay RLY3-EMSS300, 1099973 with economical pricing. Front connector with spring terminals, 24 V DC.

Brand
Sick
Model number
RLY3-EMSS300
Series
RLY3 Series
Product type
Safety Relay

Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.

Sick RLY3-EMSS300 technical specifications

Compatible sensor typesSafety sensors with potential-free outputs
Safety integrity levelSIL 3 (IEC 61508)
CategoryCategory 4 (ISO 13849-1)
Performance levelPL e (ISO 13849-1)
TM (mission time)20 years (ISO 13849-1)
Sensor monitoringDiscrepancy monitoring, Cross-circuit detection
Restart interlock✔
ResetAutomatic, Manual
External device monitoring (EDM)✔
Connection typeFront connector with spring terminals
Inputs2 safety inputs, 1 input for reset pushbutton or external device monitoring (EDM)
Outputs3 enabling current paths (safe), 2 application diagnostic outputs (not safe), 3 test pulse outputs (not safe)
Display elementsLEDs
Configuration methodHard wired
Supply voltage VS24 V DC (16.8 V ... 30 V)
Residual ripple≤ 2.4 V
Power consumption≤ 2.5 W (DC)
Input voltage HIGH24 V DC (11 V ... 30 V)
Input voltage LOW0 V DC (–3 V ... 5 V)
Input current4 mA ... 6 mA
Test pulse width-
Test pulse rate-
Response time12 ms
Type of outputN/O contacts, positively guided
Contact materialSilver alloy, gold flashed
Switching voltage10 V AC ... 230 V AC, 10 V DC ... 230 V DC
Switching current10 mA ... 6 A
Total current12 A
Overvoltage categoryIII (EN 60664-1)
Rated impulse withstand voltage Uimp6 kV (EN 60664-1)
Output voltage HIGH≥ Vs – 3 V
Output voltage LOW≤ 3 V
Input current (NPN)≤ 15 mA
Output current (PNP)≤ 120 mA
Output voltage≥ Vs – 3 V
Test pulse interval40 ms
Dimensions (W x H x D)18 mm x 124.6 mm x 85.5 mm
Enclosure ratingIP20 (IEC 60529)
Ambient operating temperature–25 °C ... +55 °C
Storage temperature–25 °C ... +70 °C
Air humidity≤ 95 %, Non-condensing
Interference emissionAccording to IEC 61000-6-4
Interference resistanceAccording to IEC 61326-3-1, According to IEC 61000-6-2, According to IEC 60947-5-1
Weight150 g
Specifications as listed by IndMALL. Confirm against the manufacturer's datasheet before ordering.

Overview

The Sick RLY3-EMSS300 Safety Relay is a high-performance safety relay designed for applications using safety sensors with potential-free outputs . As part of Sick’s advanced N/O Output Safety Relay series, the RLY3-EMSS300 provides precise control of safety circuits for machines, conveyors, and robotics systems. The RLY3-EMSS300 Safety Relay integrates superior electrical and mechanical performance for demanding safety applications. Operating at a stable 24 V DC supply voltage and consuming ≤ 2.5 W, this relay ensures energy efficiency without compromising safety. In real-world applications, the Sick RLY3-EMSS300 Safety Relay is widely used in robotic cells, packaging machines, press controls, and conveyor systems to achieve reliable emergency stop and safety gate monitoring.

Datasheet

Sick datasheetrly3-emss300-1099973.pdf

Other models in this series

Compare RLY3-EMSS300 with similar models in the same series. See all 10 models on the RLY3 Series page.

RLY3-EMSS300 compared with other models in the series
ModelConfiguration methodInput currentInput current (NPN)Output current (PNP)
RLY3-EMSS300 (this model)Hard wired4 mA ... 6 mA≤ 15 mA≤ 120 mA
RLY3-EMSS100—
RLY3-TIME100Hard wired, DIP switch4 mA ... 6 mA≤ 15 mA≤ 120 mA
RLY3-OSSD400-≤ 60 mA--
RLY3-MULT100Hard wired, DIP switch≤ 60 mA≤ 15 mA≤ 120 mA
RLY3-OSSD100-≤ 50 mA--
RLY3-HAND100Hard wired4 mA ... 6 mA≤ 15 mA≤ 120 mA
RLY3-OSSD200—