Image for reference. Refer to the datasheet for exact dimensions.
ATS480C32Y - Schneider Altistart 480 320A Soft Starter
Schneider ATS480C32Y, Altistart 480 320A Soft Starter. Boost efficiency—request your IndMALL quote today for reliable soft starter solutions.
Send this enquiry to IndMALL on WhatsApp — the model and page link are filled in. Add the quantity and your company details, and we connect you with the right suppliers.
Schneider ATS480C32Y technical specifications
| Range of Product | Altivar Soft Starter ATS480 |
|---|---|
| Motor power kW | 90.0 kW at 230 V in the motor supply line normal duty75.0 kW at 230 V in the motor supply line heavy duty160.0 kW at 400 V in the motor supply line normal duty132.0 kW at 400 V in the motor supply line heavy duty160.0 kW at 440 V in the motor supply line normal duty132.0 kW at 440 V in the motor supply line heavy duty220.0 kW at 500 V in the motor supply line normal duty160.0 kW at 500 V in the motor supply line heavy duty220.0 kW at 525 V in the motor supply line normal duty160.0 kW at 525 V in the motor supply line heavy duty250.0 kW at 660 V in the motor supply line normal duty220.0 kW at 660 V in the motor supply line heavy duty315.0 kW at 690 V in the motor supply line normal duty250.0 kW at 690 V in the motor supply line heavy duty160.0 kW at 230 V to the motor delta terminals normal duty132.0 kW at 230 V to the motor delta terminals heavy duty250.0 kW at 400 V to the motor delta terminals normal duty220.0 kW at 400 V to the motor delta terminals heavy duty |
| Rated operational current [Ie] | Normal duty: 320.0 A (at <40 °C) |
| Torque control | TRUE |
| Rated insulation voltage [Ui] | 690 V |
| Minimum switching current | 100 mA at 12 V DC for relay outputs |
| Maximum switching current | Relay outputs 2 A at 250 V ACRelay outputs 2 A at 30 V DCRelay outputs |
| Power supply frequency | 50...60 Hz - 20...20 % |
| Method of access | Slave Modbus serial |
| Package weight | 26.500 kg |
| Discrete Output Type | (DQ1) programmable digital output <= 30 V (DQ2) programmable digital output <= 30 V |
| Analog Output Number | 1 |
| Maximum acceleration under vibratory load (during storage) | 15 m/s² at 200...500 Hz10 m/s² at 9...200 Hz |
| Device Short name | ATS480 |
| Net Weight | 18.2 kg |
| IP Degree protection | IP00 |
| Output Compatibility | Open collector level 1 PLC conforming to IEC 65A-68 |
| [Uc] control circuit voltage | 24 V DC |
| Relay output number | 3 |
| Discrete input logic | Programmable digital input at State 0: < 5 V |
| Communication port protocol | Modbus serial |
| Motor Power Hp | 100.0 hp at 208 V normal duty75.0 hp at 208 V heavy duty125.0 hp at 230 V normal duty100.0 hp at 230 V heavy duty250.0 hp at 460 V normal duty200.0 hp at 460 V heavy duty300.0 hp at 575 V normal duty250.0 hp at 575 V heavy duty |
| Relay Output Type | Relay outputs R1A 1 NORelay outputs R1B 1 NORelay outputs RIC NO/NC programmable |
| Ambient air temperature for operation | 40…60 °C (with current derating of 2 % per °C)-15…40 °C (without derating) |
| data format | 8 bits, configurable odd, even or no parity |
| Pollution Degree | Level 3 |
| Ambient air temperature for storage | -25…70 °C |
| Relative Humidity | 0…95 % without condensation or dripping water conforming to IEC 60068-2-3 |
| Width | 320.0 mm |
| Ue power supply voltage | 208...690 V - 15...10 % |
| Connection Type | 1 RJ45 |
Overview
ATS480C32Y Datasheet presents the key specifications of the Schneider ATS480C32Y Soft Starter , an advanced VFD designed to control motors up to 320A at operating voltages between 208–690 V AC . Designed for reliability, the ATS480C32Y includes three relay outputs , two programmable digital outputs rated ≤30 V, and one analog output for fine-tuned control. It has an insulation voltage of 690 V and relay switching capacity of 2 A at 250 V AC or 2 A at 30 V DC . The ATS480C32Y is widely used in sectors such as cement, water treatment, mining, HVAC, and large-scale manufacturing where heavy-duty motors demand controlled startup.
Datasheet
Schneider datasheetschneider-electric-ats480c32y.pdfOther models in this series
Compare ATS480C32Y with similar models in the same series. See all 27 models on the ATS480 page.
| Model | Range of Product | Relay output number | Power supply frequency | Ue power supply voltage |
|---|---|---|---|---|
| ATS480C32Y (this model) | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C14Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C17Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C21Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C25Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C41Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C48Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C59Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |
| ATS480C66Y | Altivar Soft Starter ATS480 | 3 | 50...60 Hz - 20...20 % | 208...690 V - 15...10 % |